Document Ref: Nex8inst.doc/Rev0 09.07.00 Page 23 of 30 Originator MC Checked by AC Refer to the Installation & Commissioning Manuals for these boards. 6.6 Auxiliary Circuits Any auxiliary circuits or equipment which is not supplied as a standard part of the fire alarm panel is the responsibility of the installer and must be tested for safe and correct operation by the commissioning engineer. If special output facilities are provided as extra equipment, refer to separate drawings and manuals for commissioning information. 6.7 Cause & Effect Editing The Nexus panel may now be programmed with the text, zone and cause & effect information.
![Motorola Motorola](http://www.pdf-zoo.com/lynteck/6909/nexus-8-user-manual/preview.png)
WARNING: We strongly recommend that no cause & effect programming should be attempted without the use of the pc down-load facility due to the extensive range of options available. However, if direct panel programming is unavoidable, a separate document entitled “Programming the Nexus 1-8 Loop Analogue Addressable Control Panel Without a PC” is available.
6.7.1 Cause & Effect Testing Testing of the panel’s fire and fault relays and all cause & effect outputs must be done with the system fully functional. There are two options: (i) Operate field devices and physically check programmed output devices for correct operation. (ii) Select engineer’s option 5: STATUS and operate devices with the System Enabled option as described in the Nexus 1-8 Loop Installation Manual. This will cause selected devices to go into fire and operate the panel’s cause & effect programming. Physically check programmed output devices for correct operation.
6.8 Final Commissioning 6.8.1 Select engineer’s Option 9: DEVICE TEST and carry out tests on all sensor devices. 6.8.2 Testing of the panel’s fire and fault relays and all cause & effect outputs must be done with the system fully functional. There are two options for testing the panels cause & effect: (i) Operate devices as required (ii) Use engineer’s Option 5: STATUS, selection 1 SYSTEM ENABLED to operate devices.